Models & Ratings for A1000 600V Drive

A1000 600V AC DriveA1000 600V AC Variable Frequency Drive

1-30 Horsepower
The Drive for the Future . . . Today

 

Models & Ratings for A1000 600V Drive

A1000 600V Standard Drives – 1-10HP, 600V, 3-phase, NEMA 1 enclosure

Please note: 40-350HP (ND) are in development. Please consult your local sales representative for details.

 

Rated Input Voltage
Drive Model Number
CIMR-AU
Normal Duty (ND)1
Heavy Duty (HD)1
Standard Enclosure
Rated Output Current (Amps)
Nominal
HP2
Rated Output Current (Amps)
Nominal HP2
600V
CIMR-AU5A0003FAA
2.7
2
1.7
1
NEMA 1
CIMR-AU5A0004FAA
3.9
3
3.5
2
CIMR-AU5A0006FAA
6.1
5
4.1
3
600V
CIMR-AU5A0009FAA
9
7.5
6.3
5
NEMA 1
CIMR-AU5A0011FAA
11
10
9.8
7.5
CIMR-AU5A0017FAA
17
15
12.5
10
600V
CIMR-AU5A0022FAA
22
20
17
15
NEMA 1
CIMR-AU5A0027FAA
27
25
22
20
CIMR-AU5A0032FAA
32
30
27
25

Please note: 40-350HP (ND) are in development.

  1. Normal Duty overload current rating is 120% of rated output current for 60 seconds; Heavy Duty overload current rating is 150% of rated output current for 60 seconds
  2. Horsepower rating is based on standard NEMA B 4-pole motor design as represented in NEC table 430. 150 Full-Load Current, Three-Phase Alternating Current Motors

Model Number Designation for A1000 600V Drive

Model Number Designation for A1000 600V Drive
Copyright © 2010 Yaskawa Electric America, Inc. All Rights Reserved.